Design Principles and Technical Information
Design Planning
When you want to invest in a solar power station, you need to consider how many solar panels to install and which types of converters to install, and how many strings of modules a converter should correspond to and how many modules a group of strings contains, etc. Maximize power generation efficiency and accelerate the return on your investment.
New Monitoring Platform Power Station List
SolarEdge's new monitoring platform power station list speeds up and simplifies the power station screening function, and can view specific information according to your search criteria, making the installer's power station management simpler, faster and more efficient.
General Rules
- 1 kilowatt of solar modules can be installed per 7 square meters.
- On average, each solar module has 295 watts, 9.2 amps, 32 volts, and is composed of 60 small batteries.
- Different inverters have different The best DC voltage input.
- Each solar module is 1.8 meters long and 1 meter wide.
- Each SolarEdge power optimizer (P650) can be installed corresponding to two solar modules Design principles and technical data
Steps to Install and Design a Solar Power Plant
Single Phase Inverter (HD-Wave Technology) | SE3000H | SE4000H | SE5000H | SE6000H |
---|---|---|---|---|
Rated AC Output Power | 3000VA | 4000VA | 5000VA | 6000VA |
Maximum AC Output Power | 3000VA | 4000VA | 5000VA | 6000VA |
AC Output Voltage (Rated) | 220/230 Vac | 4000VA | 5000VA | 6000VA |
AC Voltage Range | 220/230 Vac | 220/230 Vac | 220/230 Vac | 220/230 Vac |
Rated AC Voltage Frequency | 184 – 264.5 Vac | 184 – 264.5 Vac | 184 – 264.5 Vac | 184 – 264.5 Vac |
Three Phase Inverter (SE15K – SE25K) | SE15K | SE17K |
---|---|---|
Rated AC Output Power | 15000VA | 17000VA |
Maximum AC Output Power | 15000VA | 17000VA |
AC Output Voltage – Live-to-Live/Live-to-Neutral (Standard) | 380 / 220 ; 400 / 230 Vac | 380 / 220 ; 400 / 230 Vac |
AC Output Voltage – Line to Neutral Range | 184 – 264.5 Vac | 184 – 264.5 Vac |
AC Frequency | 50/60 ± 5 Hz | 50/60 ± 5 Hz |
Support Grid - Three Phase | 3 / N / PE (WYE with neutral) V | 3 / N / PE (WYE with neutral) V |
Three Phase Inverter (for Medium Voltage Grid 277/480V) | SE33.3K |
---|---|
Rated AC Output Power | 33300VA |
Maximum AC Output Power | 33300VA |
AC Output Voltage – Live-to-Live/Live-to-Neutral (Standard) | 480 / 277 Vac |
AC Output Voltage – Line to Neutral Range | 243.8-304.7 Vac |
AC Frequency | 50/60 ± 5 Hz |
Support Grid - Three Phase | 3 / N / PE Three-phase four-wire system V |
Three Phase Inverter (for Delta Grid) | SE15K | SE17K |
---|---|---|
Rated AC Output Power | 8700VA | 10000VA |
Maximum AC Output Power | 8700VA | 10000VA |
AC Output Voltage – Live-to-Live/Live-to-Neutral (Standard) | 220 / 127 ; 230 / 133 Vac | 220 / 127 ; 230 / 133 Vac |
AC Output Voltage – Line to Neutral Range | 184 – 264.5 Vac | 184 – 264.5 Vac |
Support Grid - Three Phase | 3-wire / PE (Delta; neutral ground not supported) | 3-wire / PE (Delta; neutral ground not supported) |
Three Phase Inverter Synergy Technology | SE66.6K | SE100K | SE120K |
---|---|---|---|
Rated AC Output Power | 66600W | 100000W | 120000W |
Maximum AC Output Power | 66600VA | 100000VA | 120000VA |
AC Output Voltage – Line-to-Line/Line-to-Neutral (Standard) | 380 / 220;400 / 230 Vac | 380 / 220;400 / 230 Vac | 480 / 277 Vac |
AC Output Voltage – Line-to-Line Range / Line-to-Neutral Range | 304 - 437 / 176 - 253;320 - 478 / 184 - 264.5 Vac | 304 - 437 / 176 - 253;320 - 478 / 184 - 264.5 Vac | 432 - 529 / 249 - 305 Vac |
AC Frequency | 50/60 ± 5% Hz | 50/60 ± 5% Hz | 50/60 ± 5% Hz |
Support Grid | WYE:TN-C、TN-S、TN-C-S、TT、IT;Delta:IT | WYE:TN-C、TN-S、TN-C-S、TT、IT;Delta:IT | WYE:TN-C、TN-S、TN-C-S、TT、IT;Delta:IT |
Three Phase Inverter Synergy Technology (for 220V Grid) | SE66.6K | SE100K-TW |
---|---|---|
Rated AC Output Power | 38450W | 57700W |
Maximum AC Output Power | 38450VA | 57700VA |
AC Output Voltage – Line-to-Line/Line-to-Neutral (Standard) | 220 / 127;230 / 133 Vac | 220 / 127;230 / 133 Vac |
AC Output Voltage – Line-to-Line Range / Line-to-Neutral Range | 176 - 253 / 184 - 264.5 Vac | 176 - 253 / 184 - 264.5 Vac |
AC Frequency | 50/60 ± 5% Hz | 50/60 ± 5% Hz |
Support Grid | WYE:TN-C、TN-S、TN-C-S、TT、IT;Delta:IT | WYE:TN-C、TN-S、TN-C-S、TT、IT;Delta:IT |